OpenStudio Results

Model Summary


Information Value Units
Building Name NECB 2011-HighriseApartment-NECB HDD Method-CAN_PQ_St.Hubert.713710_CWEC.epw created: 2017-06-30 13:16:37 +0000 building_name
Net Site Energy 3,592,976 kBtu
Total Building Area 84,351 ft^2
EUI (Based on Net Site Energy and Total Building Area) 42.60 kBtu/ft^2
OpenStudio Standards Building Type HighriseApartment

Value
Weather File St Hubert PQ CAN WYEC2-B-04712 WMO#=713710
Latitude 45.52
Longitude -73.4
Elevation 89 (ft)
Time Zone -5.0
North Axis Angle 0.00
ASHRAE Climate Zone

Maximum Dry Bulb (F) Daily Temperature Range (R) Humidity Value Humidity Type Wind Speed (mph) Wind Direction
ST HUBERT ANN CLG .4% CONDNS DB=>MWB 86.18 18.54 71.24 Wetbulb [F] 11.86 240.0
ST HUBERT ANN CLG .4% CONDNS WB=>MDB 82.4 18.54 73.94 Wetbulb [F] 11.86 240.0
ST HUBERT ANN HTG 99.6% CONDNS DB -11.74 0.0 -11.74 Wetbulb [F] 7.38 270.0

Time Setpoint Not Met Time (hr)
During Heating 0.5
During Cooling 49.25
During Occupied Heating 0.5
During Occupied Cooling 43.25

Tolerance for Time Setpoint Not Met Temperature (F)
Heating 1.8
Cooling 1.8

Annual Overview

One or more tables in Annual Overview section returned false and was skipped.

End Use Consumption (kBtu)
Heating 1,690,166
Cooling 280,914
Interior Lighting 299,122
Exterior Lighting 0
Interior Equipment 468,544
Exterior Equipment 0
Fans 222,661
Pumps 2,891
Heat Rejection 256
Humidification 0
Heat Recovery 0
Water Systems 628,412
Refrigeration 0
Generators 0

Fuel Consumption (kBtu)
Electricity 3,592,976
Natural Gas 0
Additional Fuel 0
District Cooling 0
District Heating 0

End Use Consumption (kWh)
Heating 495,339
Cooling 82,328
Interior Lighting 87,664
Exterior Lighting 0
Interior Equipment 137,317
Exterior Equipment 0
Fans 65,256
Pumps 847
Heat Rejection 75
Humidification 0
Heat Recovery 0
Water Systems 184,169
Refrigeration 0
Generators 0

Monthly Overview


Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total
Heating 107308.89 80555.83 62092.22 33051.67 14654.08 5227.64 2161.99 3787.78 9992.53 27920.83 53235.28 95351.39 495340.13
Cooling 209.07 614.74 1777.49 2386.43 8131.25 15116.14 23001.33 17370.17 10138.47 2966.78 475.99 139.02 82326.88
Interior Lighting 7444.64 6725.47 7454.72 7191.47 7454.72 7211.64 7434.56 7454.72 7201.56 7444.64 7211.64 7434.56 87664.33
Exterior Lighting
Interior Equipment 11662.0 10534.06 11666.97 11279.42 11666.97 11289.33 11657.06 11666.97 11284.39 11662.0 11289.33 11657.06 137315.56
Exterior Equipment
Fans 3369.83 3204.47 3985.36 4095.56 6159.58 7918.78 10076.17 8600.92 6719.11 4419.89 3373.08 3334.08 65256.83
Pumps 23.06 33.42 52.35 72.03 92.96 101.26 113.65 109.2 93.3 76.32 55.64 24.17 847.37
Heat Rejection 0.0 0.03 0.47 1.13 5.88 15.33 22.18 17.96 10.15 1.91 0.1 0.0 75.14
Humidification
Heat Recovery
Water Systems 17057.78 15790.33 17364.56 16140.61 15888.94 14449.28 14130.64 13863.89 13594.0 14511.14 15005.14 16373.83 184170.14
Refrigeration
Generators
Total 147075.26 117458.36 104394.15 74218.31 64054.4 61329.4 68597.57 62871.61 59033.51 69003.51 90646.21 134314.11 1052996.38

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Heating 340.7661 315.3147 237.5889 97.5553 33.0106 77.2162 197.3341 309.6179
Cooling 0.3062 0.002 56.8429 78.4739 71.8491 53.8546 13.4573 0.0651 0.0247
Interior Lighting 21.5307 20.7431 20.7431 21.5307 37.5581 37.5581 37.2956 37.2956 37.2956 21.5307 21.5307 21.5307
Exterior Lighting
Interior Equipment 28.4158 28.0187 28.0187 28.4158 31.5707 31.5707 31.5045 31.5045 31.5045 28.4158 28.4158 28.4158
Exterior Equipment
Fans 4.6392 4.1967 4.6392 4.64 20.1019 24.4269 23.7187 19.2882 9.4882 4.6519 4.6392 4.6392
Pumps 0.0172 0.0172 0.1836 0.0172 0.1836 0.1836 0.1836 0.1836 0.0172 0.1836 0.0727 0.0172
Heat Rejection 0.0386 0.1167 0.0478 0.0358
Humidification
Heat Recovery
Water Systems 50.7303 28.7828 52.4975 60.7884 36.295 27.1197 52.276 52.0475 54.7261 57.5073 30.8012 60.0026
Refrigeration
Generators
Total 446.1 397.07 343.98 212.95 182.59 199.45 216.88 194.21 179.5 189.57 282.82 424.22

Utility Bills/Rates

No Data to Show for Utility Bills/Rates

Envelope


Construction Net Area (ft^2) Surface Count R Value (ft^2*h*R/Btu)
Customized opaque construction {a7487f93-7dee-4de5-8947-f4df40aeb5dc} to conductance of 0.247 29,112 140 22.99
Customized opaque construction {e59c3d97-1cfd-4e28-a086-c65521eecf3f} to conductance of 0.183 8,435 9 31.03

Construction Area (ft^2) Surface Count U-Factor (Btu/ft^2*h*R)
Customized Fenestration: cond=0.220 tvis=0.220 tsol=0.232 12,383 140 0.3874

Description Total (%) North (%) East (%) South (%) West (%)
Gross Window-Wall Ratio 29.84 30.0 29.62 30.0 29.19
Gross Window-Wall Ratio (Conditioned) 29.84 30.0 29.62 30.0 29.19
Skylight-Roof Ratio 0.0

Space Type Breakdown


Space Type Name Floor Area (ft^2) Standards Building Type Standards Space Type
Space Function Corr. < 2.4m wide-sch-G 8,359 Space Function Corr. < 2.4m wide-sch-G
Space Function Dwelling Unit(s) 75,042 Space Function Dwelling Unit(s)
Space Function Office - enclosed 950 Space Function Office - enclosed

Space Type Summary


Definition Value Unit Inst. Multiplier
Space Function Corr. < 2.4m wide-sch-G People Definition 0.0009 people/ft^2 1.0
Space Function Corr. < 2.4m wide-sch-G Lights Definition 0.7804 W/ft^2 1.0
Space Function Corr. < 2.4m wide-sch-G Ventilation (outdoor air method Sum) 0.0600 cfm/floor area ft^2

Definition Value Unit Inst. Multiplier
Space Function Dwelling Unit(s) People Definition 0.0016 people/ft^2 1.0
Space Function Dwelling Unit(s) Elec Equip Definition 0.4645 W/ft^2 1.0
Space Function Dwelling Unit(s) Lights Definition 0.4645 W/ft^2 1.0
Space Function Dwelling Unit(s) Ventilation (outdoor air method Sum) 0.0680 cfm/floor area ft^2

Definition Value Unit Inst. Multiplier
Space Function Office - enclosed People Definition 0.0046 people/ft^2 1.0
Space Function Office - enclosed Elec Equip Definition 0.6968 W/ft^2 1.0
Space Function Office - enclosed Lights Definition 1.1055 W/ft^2 1.0
Space Function Office - enclosed Ventilation (outdoor air method Sum) 0.0850 cfm/floor area ft^2

Interior Lighting Summary


Zone Lighting Power Density (W/ft^2) Total Power (W) Schedule Name Scheduled Hours/Week (hr) Actual Load Hours/Week (hr) Return Air Fraction Annual Consumption (kWh)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-G CORRIDOR SYS-6 FLR-5 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-G CORRIDOR SYS-6 FLR-5 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN SPACE FUNCTION OFFICE - ENCLOSED LIGHTS SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 1.11 1050.15 NECB-A-LIGHTING 56.27 56.27 0.0000 3080.56

Plug Loads Summary


Electricity Annual Value (kWh)
InteriorEquipment:Electricity:Zone:SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 2450.0

Exterior Lighting

No Data to Show for Exterior Lighting

Water Use Equipment


Instance Plant Loop Definition Space Peak Flow Rate (gal/min) Flow Rate Schedule Target Temp Range (F)
F2 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 n1 apartment Service Water Use Def 0.06gal/min F2 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 n2 apartment Service Water Use Def 0.06gal/min F2 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F2 ne apartment Service Water Use Def 0.06gal/min F2 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F2 nw apartment Service Water Use Def 0.06gal/min F2 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 s1 apartment Service Water Use Def 0.06gal/min F2 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 s2 apartment Service Water Use Def 0.06gal/min F2 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 se apartment Service Water Use 0.06gal/min Main Service Water Loop F2 se apartment Service Water Use Def 0.06gal/min F2 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F2 sw apartment Service Water Use Def 0.06gal/min F2 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 n1 apartment Service Water Use Def 0.06gal/min F3 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 n2 apartment Service Water Use Def 0.06gal/min F3 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F3 ne apartment Service Water Use Def 0.06gal/min F3 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F3 nw apartment Service Water Use Def 0.06gal/min F3 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 s1 apartment Service Water Use Def 0.06gal/min F3 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 s2 apartment Service Water Use Def 0.06gal/min F3 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 se apartment Service Water Use 0.06gal/min Main Service Water Loop F3 se apartment Service Water Use Def 0.06gal/min F3 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F3 sw apartment Service Water Use Def 0.06gal/min F3 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 n1 apartment Service Water Use Def 0.06gal/min F4 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 n2 apartment Service Water Use Def 0.06gal/min F4 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F4 ne apartment Service Water Use Def 0.06gal/min F4 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F4 nw apartment Service Water Use Def 0.06gal/min F4 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 s1 apartment Service Water Use Def 0.06gal/min F4 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 s2 apartment Service Water Use Def 0.06gal/min F4 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 se apartment Service Water Use 0.06gal/min Main Service Water Loop F4 se apartment Service Water Use Def 0.06gal/min F4 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F4 sw apartment Service Water Use Def 0.06gal/min F4 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 n1 apartment Service Water Use Def 0.06gal/min F6 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 n2 apartment Service Water Use Def 0.06gal/min F6 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F6 ne apartment Service Water Use Def 0.06gal/min F6 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F6 nw apartment Service Water Use Def 0.06gal/min F6 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 s1 apartment Service Water Use Def 0.06gal/min F6 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 s2 apartment Service Water Use Def 0.06gal/min F6 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 se apartment Service Water Use 0.06gal/min Main Service Water Loop F6 se apartment Service Water Use Def 0.06gal/min F6 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F6 sw apartment Service Water Use Def 0.06gal/min F6 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 n1 apartment Service Water Use Def 0.06gal/min F7 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 n2 apartment Service Water Use Def 0.06gal/min F7 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F7 ne apartment Service Water Use Def 0.06gal/min F7 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F7 nw apartment Service Water Use Def 0.06gal/min F7 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 s1 apartment Service Water Use Def 0.06gal/min F7 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 s2 apartment Service Water Use Def 0.06gal/min F7 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 se apartment Service Water Use 0.06gal/min Main Service Water Loop F7 se apartment Service Water Use Def 0.06gal/min F7 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F7 sw apartment Service Water Use Def 0.06gal/min F7 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 n1 apartment Service Water Use Def 0.06gal/min F8 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 n2 apartment Service Water Use Def 0.06gal/min F8 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F8 ne apartment Service Water Use Def 0.06gal/min F8 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F8 nw apartment Service Water Use Def 0.06gal/min F8 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 s1 apartment Service Water Use Def 0.06gal/min F8 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 s2 apartment Service Water Use Def 0.06gal/min F8 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 se apartment Service Water Use 0.06gal/min Main Service Water Loop F8 se apartment Service Water Use Def 0.06gal/min F8 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F8 sw apartment Service Water Use Def 0.06gal/min F8 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 n1 apartment Service Water Use Def 0.06gal/min F9 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 n2 apartment Service Water Use Def 0.06gal/min F9 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F9 ne apartment Service Water Use Def 0.06gal/min F9 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F9 nw apartment Service Water Use Def 0.06gal/min F9 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 s1 apartment Service Water Use Def 0.06gal/min F9 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 s2 apartment Service Water Use Def 0.06gal/min F9 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 se apartment Service Water Use 0.06gal/min Main Service Water Loop F9 se apartment Service Water Use Def 0.06gal/min F9 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F9 sw apartment Service Water Use Def 0.06gal/min F9 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G n1 apartment Service Water Use 0.06gal/min Main Service Water Loop G n1 apartment Service Water Use Def 0.06gal/min G N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G n2 apartment Service Water Use 0.06gal/min Main Service Water Loop G n2 apartment Service Water Use Def 0.06gal/min G N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G ne apartment Service Water Use 0.06gal/min Main Service Water Loop G ne apartment Service Water Use Def 0.06gal/min G NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G nw apartment Service Water Use 0.06gal/min Main Service Water Loop G nw apartment Service Water Use Def 0.06gal/min G NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G s1 apartment Service Water Use 0.06gal/min Main Service Water Loop G s1 apartment Service Water Use Def 0.06gal/min G S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G s2 apartment Service Water Use 0.06gal/min Main Service Water Loop G s2 apartment Service Water Use Def 0.06gal/min G S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G sw apartment Service Water Use 0.06gal/min Main Service Water Loop G sw apartment Service Water Use Def 0.06gal/min G SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M n1 apartment Service Water Use 0.06gal/min Main Service Water Loop M n1 apartment Service Water Use Def 0.06gal/min M N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M n2 apartment Service Water Use 0.06gal/min Main Service Water Loop M n2 apartment Service Water Use Def 0.06gal/min M N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M ne apartment Service Water Use 0.06gal/min Main Service Water Loop M ne apartment Service Water Use Def 0.06gal/min M NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M nw apartment Service Water Use 0.06gal/min Main Service Water Loop M nw apartment Service Water Use Def 0.06gal/min M NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M s1 apartment Service Water Use 0.06gal/min Main Service Water Loop M s1 apartment Service Water Use Def 0.06gal/min M S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M s2 apartment Service Water Use 0.06gal/min Main Service Water Loop M s2 apartment Service Water Use Def 0.06gal/min M S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M se apartment Service Water Use 0.06gal/min Main Service Water Loop M se apartment Service Water Use Def 0.06gal/min M SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M sw apartment Service Water Use 0.06gal/min Main Service Water Loop M sw apartment Service Water Use Def 0.06gal/min M SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
Office Service Water Use 0.03gal/min Main Service Water Loop Office Service Water Use Def 0.03gal/min Office 0.03 NECB-A-Service Water Heating 140.0 to 140.0
T n1 apartment Service Water Use 0.06gal/min Main Service Water Loop T n1 apartment Service Water Use Def 0.06gal/min T N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T n2 apartment Service Water Use 0.06gal/min Main Service Water Loop T n2 apartment Service Water Use Def 0.06gal/min T N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T ne apartment Service Water Use 0.06gal/min Main Service Water Loop T ne apartment Service Water Use Def 0.06gal/min T NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T nw apartment Service Water Use 0.06gal/min Main Service Water Loop T nw apartment Service Water Use Def 0.06gal/min T NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T s1 apartment Service Water Use 0.06gal/min Main Service Water Loop T s1 apartment Service Water Use Def 0.06gal/min T S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T s2 apartment Service Water Use 0.06gal/min Main Service Water Loop T s2 apartment Service Water Use Def 0.06gal/min T S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T se apartment Service Water Use 0.06gal/min Main Service Water Loop T se apartment Service Water Use Def 0.06gal/min T SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T sw apartment Service Water Use 0.06gal/min Main Service Water Loop T sw apartment Service Water Use Def 0.06gal/min T SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0

HVAC Load Profiles


Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Average Outdoor Air Dry Bulb (F) 14.0 16.4 27.0 41.6 56.1 64.9 70.1 67.2 58.9 46.1 34.5 19.0
Cooling Load (MBtu) 0.71 2.1 6.07 8.14 27.74 51.58 78.48 59.27 34.59 10.12 1.62 0.47
Heating Load (MBtu) 366.15 274.87 211.87 112.78 50.0 17.84 7.38 12.92 34.1 95.27 181.65 325.35

Zone Conditions


Zone Unmet Htg (hr) Unmet Htg - Occ (hr) < 56 (F) 56-61 (F) 61-66 (F) 66-68 (F) 68-70 (F) 70-72 (F) 72-74 (F) 74-76 (F) 76-78 (F) 78-83 (F) 83-88 (F) >= 88 (F) Unmet Clg (hr) Unmet Clg - Occ (hr) Mean Temp (F)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 24 406 2028 1376 4919 7 0 0 0 0 0 73.5 (F)
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 31 319 542 2844 940 4061 23 0 0 0 1 1 72.9 (F)
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 32 323 542 2860 917 4065 21 0 0 0 1 1 72.9 (F)
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 312 395 397 2967 670 4009 10 0 0 0 3 3 72.6 (F)
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 300 388 407 2927 712 4002 24 0 0 0 4 4 72.7 (F)
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 1 84 288 1201 1255 5909 21 1 0 0 6 6 73.9 (F)
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 1 91 283 1201 1251 5909 22 2 0 0 6 6 73.9 (F)
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 140 253 401 1788 951 5203 24 0 0 0 5 5 73.4 (F)
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 116 258 415 1816 933 5201 21 0 0 0 1 1 73.4 (F)
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 24 386 1976 1355 5011 8 0 0 0 0 0 73.6 (F)
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 42 317 524 2783 919 4150 25 0 0 0 1 1 72.9 (F)
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 44 321 521 2788 910 4149 27 0 0 0 1 1 72.9 (F)
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 328 387 378 2957 631 4067 12 0 0 0 3 3 72.6 (F)
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 317 373 394 2907 695 4050 24 0 0 0 4 4 72.7 (F)
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 2 89 271 1158 1236 5980 23 1 0 0 6 6 73.9 (F)
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 2 89 274 1160 1240 5971 23 1 0 0 6 6 73.9 (F)
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 134 259 385 1815 921 5218 28 0 0 0 6 6 73.4 (F)
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 131 253 394 1825 900 5235 22 0 0 0 2 2 73.4 (F)
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 25 398 1980 1339 5009 9 0 0 0 0 0 73.6 (F)
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 56 329 501 2785 912 4151 26 0 0 0 1 1 72.9 (F)
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 56 334 500 2795 888 4159 28 0 0 0 1 1 72.9 (F)
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 350 372 379 2967 628 4051 13 0 0 0 3 3 72.6 (F)
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 333 374 382 2920 688 4039 24 0 0 0 4 4 72.7 (F)
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 4 96 282 1186 1219 5950 22 1 0 0 6 6 73.9 (F)
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 4 96 288 1190 1212 5945 24 1 0 0 6 6 73.9 (F)
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 149 265 383 1842 914 5176 31 0 0 0 8 8 73.3 (F)
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 142 262 382 1859 895 5198 22 0 0 0 2 2 73.3 (F)
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 32 421 2036 1322 4940 9 0 0 0 0 0 73.5 (F)
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 84 342 490 2841 890 4089 24 0 0 0 1 1 72.9 (F)
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 86 346 480 2859 883 4085 21 0 0 0 0 0 72.9 (F)
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 386 366 370 3018 628 3976 16 0 0 0 3 3 72.6 (F)
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 372 363 386 2956 688 3971 24 0 0 0 4 4 72.6 (F)
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 13 107 307 1296 1184 5830 23 0 0 0 5 5 73.8 (F)
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 13 109 307 1299 1187 5822 22 1 0 0 5 5 73.8 (F)
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 177 283 382 1918 899 5066 35 0 0 0 9 9 73.3 (F)
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 175 274 380 1931 887 5089 24 0 0 0 2 2 73.3 (F)
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 39 444 2096 1297 4875 9 0 0 0 0 0 73.5 (F)
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 92 361 480 2926 863 4017 21 0 0 0 1 1 72.8 (F)
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 92 364 479 2940 843 4024 18 0 0 0 0 0 72.8 (F)
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 401 365 375 3048 628 3927 16 0 0 0 3 3 72.6 (F)
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 388 363 388 2981 712 3904 24 0 0 0 4 4 72.6 (F)
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 15 119 330 1361 1158 5754 23 0 0 0 5 5 73.8 (F)
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 15 120 332 1372 1154 5744 22 1 0 0 4 4 73.8 (F)
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 186 295 389 1964 885 5006 35 0 0 0 9 9 73.2 (F)
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 185 288 380 1970 888 5026 23 0 0 0 2 2 73.2 (F)
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 48 483 2223 1271 4726 9 0 0 0 0 0 73.4 (F)
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 111 372 487 3045 826 3900 19 0 0 0 1 1 72.7 (F)
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 112 374 485 3053 810 3911 15 0 0 0 0 0 72.7 (F)
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 427 354 398 3079 630 3855 17 0 0 0 3 3 72.5 (F)
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 406 364 394 3027 720 3826 23 0 0 0 4 4 72.5 (F)
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 28 133 359 1515 1099 5603 23 0 0 0 4 4 73.7 (F)
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 28 134 366 1509 1106 5595 21 1 0 0 4 4 73.7 (F)
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 216 303 389 2062 839 4916 35 0 0 0 9 9 73.2 (F)
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 208 301 395 2033 875 4924 24 0 0 0 2 2 73.2 (F)
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 109 555 2535 1172 4381 8 0 0 0 0 0 73.2 (F)
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 174 388 520 3182 808 3679 9 0 0 0 0 0 72.6 (F)
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 179 384 524 3183 806 3677 7 0 0 0 0 0 72.6 (F)
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 484 378 378 3166 678 3655 21 0 0 0 3 3 72.4 (F)
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 471 377 389 3109 748 3641 25 0 0 0 4 4 72.4 (F)
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 50 191 448 1786 1082 5182 21 0 0 0 4 4 73.4 (F)
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 50 191 451 1795 1084 5167 22 0 0 0 4 4 73.4 (F)
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 286 343 388 2237 849 4635 22 0 0 0 4 4 73.0 (F)
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 285 326 405 2210 898 4612 24 0 0 0 2 2 73.0 (F)
SP-G CORRIDOR SYS-6 FLR-5 SCH-G HPLCMT-EAST ZN 0 0 0 0 4 132 528 2604 1214 4247 31 0 0 0 7 7 73.3 (F)
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 55 384 551 2994 1034 3735 7 0 0 0 0 0 72.7 (F)
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 56 385 555 3010 1011 3739 4 0 0 0 0 0 72.7 (F)
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 368 399 413 3023 765 3785 7 0 0 0 3 3 72.5 (F)
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 348 410 415 2978 844 3741 24 0 0 0 5 5 72.5 (F)
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 7 114 422 1410 1326 5455 23 3 0 0 11 11 73.7 (F)
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 7 123 417 1413 1316 5457 24 3 0 0 11 11 73.7 (F)
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 154 324 455 1934 989 4878 26 0 0 0 4 4 73.2 (F)
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 26 412 2005 1327 4981 9 0 0 0 0 0 73.6 (F)
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 72 336 483 2814 899 4130 26 0 0 0 1 1 72.9 (F)
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 73 336 489 2825 879 4135 23 0 0 0 1 1 72.9 (F)
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 369 371 368 2995 630 4011 16 0 0 0 3 3 72.6 (F)
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 358 365 379 2935 691 4008 24 0 0 0 4 4 72.6 (F)
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 6 103 297 1235 1202 5894 22 1 0 0 6 6 73.9 (F)
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 7 102 297 1233 1204 5893 23 1 0 0 5 5 73.9 (F)
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 166 270 383 1880 910 5119 32 0 0 0 8 8 73.3 (F)
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 159 271 371 1906 889 5140 24 0 0 0 2 2 73.3 (F)
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 0 0 0 0 434 597 658 1587 1658 3197 341 271 17 0 10 4 72.7 (F)
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 0 0 0 0 631 367 395 3079 920 3365 3 0 0 0 0 0 72.2 (F)
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1 1 0 0 876 357 281 3555 796 2893 2 0 0 0 0 0 71.8 (F)
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1 1 0 0 876 358 275 3559 797 2893 2 0 0 0 0 0 71.8 (F)
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0 0 0 0 1012 265 267 3540 679 2980 16 1 0 0 6 6 71.8 (F)
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0 0 0 0 1014 270 302 3487 715 2948 21 3 0 0 9 9 71.8 (F)
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 742 337 327 2685 936 3714 17 2 0 0 8 8 72.3 (F)
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 742 333 328 2693 931 3715 16 2 0 0 8 8 72.3 (F)
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 913 268 277 2876 792 3596 34 4 0 0 18 18 72.1 (F)
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 920 276 312 2849 822 3553 27 1 0 0 10 10 72.1 (F)

Zone < 30 (%) 30-35 (%) 35-40 (%) 40-45 (%) 45-50 (%) 50-55 (%) 55-60 (%) 60-65 (%) 65-70 (%) 70-75 (%) 75-80 (%) >= 80 (%) Mean Relative Humidity (%)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 4897 703 754 863 664 480 324 64 11 0 0 0 28.3 (%)
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 3270 944 918 866 925 743 555 376 141 22 0 0 36.6 (%)
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 3266 951 920 858 927 748 552 381 134 23 0 0 36.6 (%)
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 3343 926 899 904 988 783 528 287 75 27 0 0 36.0 (%)
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 3343 932 919 921 1000 753 532 252 82 26 0 0 35.9 (%)
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 3634 906 977 887 896 699 390 298 64 9 0 0 34.7 (%)
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 3628 901 975 902 888 707 387 302 61 9 0 0 34.7 (%)
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 3586 872 959 936 1006 716 412 208 52 13 0 0 34.8 (%)
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 3579 872 924 980 991 717 408 222 52 15 0 0 34.8 (%)
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 4924 688 764 861 653 484 321 61 4 0 0 0 28.2 (%)
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 3317 954 907 883 904 732 539 389 115 20 0 0 36.4 (%)
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 3315 950 916 876 917 728 536 387 115 20 0 0 36.4 (%)
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 3395 924 896 905 974 771 523 281 67 24 0 0 35.8 (%)
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 3395 936 903 917 1006 735 518 263 67 20 0 0 35.7 (%)
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 3691 898 962 917 866 697 370 303 52 4 0 0 34.5 (%)
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 3679 908 956 921 859 708 370 305 49 5 0 0 34.5 (%)
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 3632 874 938 934 990 711 395 222 50 14 0 0 34.6 (%)
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 3627 876 914 971 990 706 395 224 44 13 0 0 34.6 (%)
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 4926 690 764 859 652 484 321 60 4 0 0 0 28.2 (%)
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 3342 946 907 876 905 720 539 389 117 19 0 0 36.3 (%)
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 3342 944 913 868 919 722 531 389 113 19 0 0 36.3 (%)
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 3428 919 884 901 967 762 520 287 69 23 0 0 35.6 (%)
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 3422 945 885 917 994 726 514 271 66 20 0 0 35.5 (%)
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 3708 899 958 910 865 691 372 299 54 4 0 0 34.4 (%)
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 3703 903 948 915 859 703 369 306 50 4 0 0 34.4 (%)
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 3657 871 925 932 977 708 392 235 49 14 0 0 34.5 (%)
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 3652 875 903 969 974 703 397 229 45 13 0 0 34.5 (%)
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 4920 693 761 864 649 481 325 63 4 0 0 0 28.2 (%)
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 3359 945 895 874 901 717 540 386 123 20 0 0 36.2 (%)
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 3359 945 898 867 915 709 542 388 117 20 0 0 36.2 (%)
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 3459 917 881 878 952 762 523 291 71 26 0 0 35.5 (%)
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 3459 942 872 906 977 718 519 275 70 22 0 0 35.4 (%)
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 3717 902 952 903 853 696 370 306 56 5 0 0 34.4 (%)
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 3713 904 943 907 851 706 369 309 53 5 0 0 34.4 (%)
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 3682 870 918 918 961 705 393 247 51 15 0 0 34.4 (%)
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 3680 869 907 949 962 701 398 235 45 14 0 0 34.4 (%)
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 4910 700 760 864 651 480 323 68 4 0 0 0 28.2 (%)
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 3358 947 891 870 902 716 543 387 126 20 0 0 36.2 (%)
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 3358 944 891 869 913 715 542 385 123 20 0 0 36.2 (%)
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 3467 912 885 869 949 755 530 287 80 26 0 0 35.5 (%)
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 3468 935 873 904 975 711 523 268 79 24 0 0 35.4 (%)
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 3715 903 946 902 855 699 372 304 59 5 0 0 34.4 (%)
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 3706 910 940 904 852 707 367 313 55 6 0 0 34.4 (%)
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 3689 867 917 911 957 706 394 252 51 16 0 0 34.4 (%)
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 3681 871 913 944 957 698 398 238 46 14 0 0 34.4 (%)
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 4883 719 757 860 662 475 326 69 9 0 0 0 28.3 (%)
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 3345 951 875 868 907 728 552 380 133 21 0 0 36.3 (%)
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 3345 948 878 860 923 724 552 382 127 21 0 0 36.3 (%)
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 3473 908 881 863 941 753 539 284 89 29 0 0 35.5 (%)
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 3463 936 873 898 972 706 535 260 89 28 0 0 35.4 (%)
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 3695 902 943 896 875 698 377 302 65 7 0 0 34.5 (%)
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 3689 905 937 903 869 705 374 306 64 8 0 0 34.5 (%)
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 3692 864 917 900 953 715 392 252 58 17 0 0 34.4 (%)
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 3680 869 904 943 952 703 403 236 55 15 0 0 34.4 (%)
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 4838 719 740 872 686 489 320 84 12 0 0 0 28.5 (%)
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 3318 938 854 865 897 769 575 358 157 29 0 0 36.5 (%)
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 3316 936 858 858 905 767 577 366 148 29 0 0 36.5 (%)
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 3459 899 869 859 946 758 551 273 109 35 2 0 35.6 (%)
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 3443 935 853 897 959 728 550 254 110 30 1 0 35.6 (%)
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 3615 915 937 896 907 697 402 305 70 16 0 0 34.8 (%)
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 3615 911 929 905 893 716 401 301 73 16 0 0 34.8 (%)
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 3644 886 952 919 953 710 396 201 75 24 0 0 34.4 (%)
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 3646 877 878 949 951 693 441 228 75 22 0 0 34.6 (%)
SP-G CORRIDOR SYS-6 FLR-5 SCH-G HPLCMT-EAST ZN 3068 763 801 3134 605 217 86 31 35 14 4 2 34.4 (%)
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 3122 972 875 829 907 787 595 392 232 40 9 0 37.5 (%)
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 3122 973 870 839 901 790 597 395 226 38 9 0 37.5 (%)
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 3203 925 891 879 949 826 576 320 136 44 11 0 36.9 (%)
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 3216 926 888 890 996 760 586 309 139 41 9 0 36.9 (%)
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 3470 915 922 860 906 712 491 310 143 28 3 0 35.7 (%)
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 3470 906 919 867 901 716 499 309 145 26 2 0 35.7 (%)
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 3435 893 909 913 997 722 508 235 112 32 4 0 35.7 (%)
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 4926 689 766 857 651 485 321 61 4 0 0 0 28.2 (%)
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 3355 941 903 875 904 717 537 391 118 19 0 0 36.2 (%)
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 3354 941 909 867 915 716 535 391 112 20 0 0 36.2 (%)
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 3443 919 885 888 959 762 525 285 69 25 0 0 35.6 (%)
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 3441 945 877 913 984 719 520 274 67 20 0 0 35.5 (%)
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 3716 898 956 906 857 694 372 301 56 4 0 0 34.4 (%)
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 3709 904 948 908 856 704 366 309 51 5 0 0 34.4 (%)
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 3673 872 915 926 969 704 392 245 49 15 0 0 34.4 (%)
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 3673 867 907 953 970 701 399 232 45 13 0 0 34.4 (%)
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 3636 849 962 1724 1498 78 13 0 0 0 0 0 32.5 (%)
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 4733 701 741 772 657 527 359 158 97 15 0 0 29.2 (%)
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 3633 886 757 764 869 646 520 382 211 82 10 0 35.3 (%)
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 3632 887 755 770 858 659 510 389 207 83 10 0 35.3 (%)
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 3713 841 758 789 809 691 500 372 184 89 14 0 35.0 (%)
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 3713 830 760 792 871 653 504 346 191 87 13 0 34.9 (%)
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 3772 833 778 803 829 629 502 341 189 78 6 0 34.7 (%)
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 3771 830 779 794 841 622 502 346 190 79 6 0 34.7 (%)
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 3824 795 801 812 827 642 486 316 172 76 9 0 34.4 (%)
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 3822 793 782 835 854 641 463 307 175 79 9 0 34.3 (%)

Zone Overview


Area (ft^2) Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume (ft^3) Multiplier Above Ground Gross Wall Area (ft^2) Underground Gross Wall Area (ft^2) Window Glass Area (ft^2) Lighting (W/ft^2) People (ft^2/person) Plug and Process (W/ft^2)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-G CORRIDOR SYS-6 FLR-5 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 48.11 0.78 1075.31 0.0
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 1.11 215.06 0.7
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 24.0 0.78 1075.31 0.0
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 113.99 0.46 645.19 0.46
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 189.01 0.46 645.19 0.46
Total 84351.17 843456.88 41495.09 0.0 12382.7 0.5 656.38 0.42
Conditioned Total 84351.17 843456.88 41495.09 0.0 12382.7 0.5 656.38 0.42
Unconditioned Total 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Not Part of Total 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Heating/Cooling Calculated Design Load Design Load With Sizing Factor Calculated Design Air Flow (ft^3/min) Design Air Flow With Sizing Factor (ft^3/min) Date/Time Of Peak Outdoor Temperature at Peak Load (F) Outdoor Humidity Ratio at Peak Load (lbWater/lbAir)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN Cooling 0.33 (ton) 0.37 (ton) 184.34 203.41 7/21 20:00:00 76.91 0.01
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN Heating 5.6 (kBtu/h) 7.28 (kBtu/h) 133.49 171.63 1/21 09:00:00 -11.74 0.0
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.29 (ton) 0.32 (ton) 163.15 177.99 7/21 20:00:00 76.91 0.01
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 5.58 (kBtu/h) 7.25 (kBtu/h) 135.61 175.87 1/21 09:30:00 -11.74 0.0
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.29 (ton) 0.32 (ton) 158.92 175.87 7/21 20:00:00 76.91 0.01
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 5.57 (kBtu/h) 7.25 (kBtu/h) 135.61 175.87 1/21 09:30:00 -11.74 0.0
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.56 (ton) 0.62 (ton) 311.48 343.26 7/21 09:00:00 75.99 0.01
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 8.37 (kBtu/h) 10.88 (kBtu/h) 201.29 262.74 1/21 09:30:00 -11.74 0.0
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.61 (ton) 0.67 (ton) 336.9 370.8 7/21 17:00:00 83.59 0.01
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 8.42 (kBtu/h) 10.95 (kBtu/h) 203.41 264.86 1/21 09:30:00 -11.74 0.0
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.4 (ton) 0.44 (ton) 218.24 241.55 7/21 13:15:00 85.48 0.01
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 5.58 (kBtu/h) 7.25 (kBtu/h) 135.61 175.87 1/21 09:30:00 -11.74 0.0
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.4 (ton) 0.44 (ton) 222.48 245.79 7/21 13:15:00 85.48 0.01
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 5.58 (kBtu/h) 7.26 (kBtu/h) 135.61 175.87 1/21 09:30:00 -11.74 0.0
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.62 (ton) 0.68 (ton) 341.14 375.04 7/21 09:00:00 75.99 0.01
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 8.41 (kBtu/h) 10.93 (kBtu/h) 203.41 264.86 1/21 09:30:00 -11.74 0.0
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.7 (ton) 0.77 (ton) 387.76 428.01 7/21 17:00:00 83.59 0.01
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 8.42 (kBtu/h) 10.95 (kBtu/h) 203.41 264.86 1/21 09:30:00 -11.74 0.0
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN Cooling 0.33 (ton) 0.37 (ton) 184.34 203.41 7/21 20:00:00 76.91 0.01
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN Heating 5.53 (kBtu/h) 7.19 (kBtu/h) 131.37 169.51 1/21 09:00:00 -11.74 0.0
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.3 (ton) 0.33 (ton) 165.27 182.22 7/21 20:00:00 76.91 0.01
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 5.65 (kBtu/h) 7.35 (kBtu/h) 135.61 177.99 1/21 09:30:00 -11.74 0.0
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.29 (ton) 0.32 (ton) 163.15 177.99 7/21 20:00:00 76.91 0.01
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 5.65 (kBtu/h) 7.34 (kBtu/h) 135.61 177.99 1/21 09:30:00 -11.74 0.0
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.57 (ton) 0.63 (ton) 315.71 347.5 7/21 09:00:00 75.99 0.01
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 8.51 (kBtu/h) 11.06 (kBtu/h) 205.53 266.98 1/21 09:30:00 -11.74 0.0
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.62 (ton) 0.68 (ton) 341.14 375.04 7/21 17:00:00 83.59 0.01
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 8.56 (kBtu/h) 11.13 (kBtu/h) 207.65 269.1 1/21 09:30:00 -11.74 0.0
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.4 (ton) 0.44 (ton) 222.48 245.79 7/21 13:15:00 85.48 0.01
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 5.65 (kBtu/h) 7.35 (kBtu/h) 135.61 177.99 1/21 09:30:00 -11.74 0.0
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.41 (ton) 0.45 (ton) 226.72 247.91 7/21 13:15:00 85.48 0.01
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 5.65 (kBtu/h) 7.34 (kBtu/h) 135.61 177.99 1/21 09:30:00 -11.74 0.0
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.6 (ton) 0.66 (ton) 332.66 366.57 7/21 09:00:00 75.99 0.01
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 8.52 (kBtu/h) 11.07 (kBtu/h) 205.53 266.98 1/21 09:30:00 -11.74 0.0
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.71 (ton) 0.78 (ton) 391.99 430.13 7/21 17:00:00 83.59 0.01
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 8.56 (kBtu/h) 11.13 (kBtu/h) 207.65 269.1 1/21 09:30:00 -11.74 0.0
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN Cooling 0.33 (ton) 0.37 (ton) 184.34 203.41 7/21 20:00:00 76.91 0.01
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN Heating 5.57 (kBtu/h) 7.25 (kBtu/h) 131.37 171.63 1/21 09:00:00 -11.74 0.0
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.3 (ton) 0.33 (ton) 165.27 182.22 7/21 20:00:00 76.91 0.01
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 5.74 (kBtu/h) 7.47 (kBtu/h) 137.73 180.1 1/21 09:30:00 -11.74 0.0
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.3 (ton) 0.32 (ton) 163.15 180.1 7/21 20:00:00 76.91 0.01
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 5.74 (kBtu/h) 7.46 (kBtu/h) 137.73 180.1 1/21 09:30:00 -11.74 0.0
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.57 (ton) 0.63 (ton) 315.71 347.5 7/21 09:00:00 75.99 0.01
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 8.64 (kBtu/h) 11.23 (kBtu/h) 209.77 271.22 1/21 09:30:00 -11.74 0.0
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.62 (ton) 0.68 (ton) 341.14 377.16 7/21 17:00:00 83.59 0.01
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 8.7 (kBtu/h) 11.31 (kBtu/h) 209.77 273.34 1/21 09:30:00 -11.74 0.0
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.41 (ton) 0.45 (ton) 224.6 245.79 7/21 13:15:00 85.48 0.01
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 5.74 (kBtu/h) 7.47 (kBtu/h) 137.73 180.1 1/21 09:30:00 -11.74 0.0
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.41 (ton) 0.45 (ton) 226.72 250.03 7/21 13:15:00 85.48 0.01
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 5.74 (kBtu/h) 7.46 (kBtu/h) 137.73 180.1 1/21 09:30:00 -11.74 0.0
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.6 (ton) 0.66 (ton) 332.66 364.45 7/21 09:00:00 75.99 0.01
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 8.64 (kBtu/h) 11.23 (kBtu/h) 207.65 271.22 1/21 09:30:00 -11.74 0.0
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.71 (ton) 0.78 (ton) 391.99 432.25 7/21 17:00:00 83.59 0.01
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 8.7 (kBtu/h) 11.31 (kBtu/h) 209.77 273.34 1/21 09:30:00 -11.74 0.0
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN Cooling 0.33 (ton) 0.37 (ton) 184.34 203.41 7/21 20:00:00 76.91 0.01
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN Heating 5.66 (kBtu/h) 7.36 (kBtu/h) 133.49 173.75 1/21 09:00:00 -11.74 0.0
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.3 (ton) 0.33 (ton) 167.39 182.22 7/21 20:00:00 76.91 0.01
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 5.89 (kBtu/h) 7.66 (kBtu/h) 141.96 184.34 1/21 09:30:00 -11.74 0.0
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.3 (ton) 0.33 (ton) 163.15 180.1 7/21 20:00:00 76.91 0.01
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 5.89 (kBtu/h) 7.66 (kBtu/h) 141.96 184.34 1/21 09:30:00 -11.74 0.0
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.57 (ton) 0.63 (ton) 315.71 347.5 7/21 09:00:00 75.99 0.01
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 8.85 (kBtu/h) 11.51 (kBtu/h) 214.01 277.57 1/21 09:30:00 -11.74 0.0
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.62 (ton) 0.68 (ton) 343.26 377.16 7/21 17:00:00 83.59 0.01
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 8.91 (kBtu/h) 11.59 (kBtu/h) 216.13 279.69 1/21 09:30:00 -11.74 0.0
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.41 (ton) 0.45 (ton) 224.6 247.91 7/21 13:15:00 85.48 0.01
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 5.89 (kBtu/h) 7.66 (kBtu/h) 141.96 184.34 1/21 09:30:00 -11.74 0.0
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.41 (ton) 0.45 (ton) 226.72 250.03 7/21 13:15:00 85.48 0.01
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 5.89 (kBtu/h) 7.66 (kBtu/h) 141.96 184.34 1/21 09:30:00 -11.74 0.0
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.6 (ton) 0.66 (ton) 330.55 364.45 7/21 09:00:00 75.99 0.01
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 8.85 (kBtu/h) 11.51 (kBtu/h) 214.01 277.57 1/21 09:30:00 -11.74 0.0
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.71 (ton) 0.78 (ton) 394.11 432.25 7/21 17:00:00 83.59 0.01
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 8.91 (kBtu/h) 11.59 (kBtu/h) 216.13 279.69 1/21 09:30:00 -11.74 0.0
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN Cooling 0.33 (ton) 0.37 (ton) 184.34 203.41 7/21 20:00:00 76.91 0.01
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN Heating 5.71 (kBtu/h) 7.42 (kBtu/h) 135.61 175.87 1/21 09:00:00 -11.74 0.0
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.3 (ton) 0.33 (ton) 167.39 182.22 7/21 20:00:00 76.91 0.01
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 5.97 (kBtu/h) 7.76 (kBtu/h) 144.08 186.46 1/21 09:30:00 -11.74 0.0
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.3 (ton) 0.33 (ton) 163.15 180.1 7/21 20:00:00 76.91 0.01
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 5.96 (kBtu/h) 7.75 (kBtu/h) 144.08 186.46 1/21 09:30:00 -11.74 0.0
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.57 (ton) 0.63 (ton) 315.71 347.5 7/21 09:00:00 75.99 0.01
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 8.95 (kBtu/h) 11.64 (kBtu/h) 216.13 281.81 1/21 09:30:00 -11.74 0.0
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.62 (ton) 0.68 (ton) 343.26 377.16 7/21 17:00:00 83.59 0.01
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 9.01 (kBtu/h) 11.72 (kBtu/h) 218.24 283.93 1/21 09:30:00 -11.74 0.0
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.41 (ton) 0.45 (ton) 224.6 247.91 7/21 13:15:00 85.48 0.01
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 5.97 (kBtu/h) 7.76 (kBtu/h) 144.08 186.46 1/21 09:30:00 -11.74 0.0
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.41 (ton) 0.45 (ton) 226.72 250.03 7/21 13:15:00 85.48 0.01
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 5.96 (kBtu/h) 7.75 (kBtu/h) 144.08 186.46 1/21 09:30:00 -11.74 0.0
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.6 (ton) 0.66 (ton) 330.55 364.45 7/21 09:00:00 75.99 0.01
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 8.95 (kBtu/h) 11.64 (kBtu/h) 216.13 281.81 1/21 09:30:00 -11.74 0.0
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.71 (ton) 0.78 (ton) 394.11 432.25 7/21 16:45:00 83.95 0.01
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 9.01 (kBtu/h) 11.72 (kBtu/h) 218.24 283.93 1/21 09:30:00 -11.74 0.0
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN Cooling 0.34 (ton) 0.37 (ton) 184.34 203.41 7/21 20:00:00 76.91 0.01
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN Heating 5.85 (kBtu/h) 7.6 (kBtu/h) 137.73 180.1 1/21 09:00:00 -11.74 0.0
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.3 (ton) 0.33 (ton) 167.39 184.34 7/21 20:00:00 76.91 0.01
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 6.1 (kBtu/h) 7.94 (kBtu/h) 148.32 190.7 1/21 09:30:00 -11.74 0.0
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.3 (ton) 0.33 (ton) 165.27 180.1 7/21 20:00:00 76.91 0.01
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 6.1 (kBtu/h) 7.93 (kBtu/h) 148.32 190.7 1/21 09:30:00 -11.74 0.0
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.57 (ton) 0.63 (ton) 313.59 345.38 7/21 09:00:00 75.99 0.01
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 9.11 (kBtu/h) 11.84 (kBtu/h) 220.36 286.05 1/21 09:30:00 -11.74 0.0
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.62 (ton) 0.68 (ton) 343.26 377.16 7/21 17:00:00 83.59 0.01
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 9.17 (kBtu/h) 11.92 (kBtu/h) 222.48 288.17 1/21 09:30:00 -11.74 0.0
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.41 (ton) 0.45 (ton) 224.6 247.91 7/21 13:15:00 85.48 0.01
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 6.1 (kBtu/h) 7.94 (kBtu/h) 148.32 190.7 1/21 09:30:00 -11.74 0.0
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.41 (ton) 0.45 (ton) 226.72 250.03 7/21 13:15:00 85.48 0.01
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 6.1 (kBtu/h) 7.93 (kBtu/h) 148.32 190.7 1/21 09:30:00 -11.74 0.0
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.6 (ton) 0.66 (ton) 330.55 362.33 7/21 09:00:00 75.99 0.01
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 9.11 (kBtu/h) 11.84 (kBtu/h) 220.36 286.05 1/21 09:30:00 -11.74 0.0
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.71 (ton) 0.78 (ton) 394.11 432.25 7/21 17:00:00 83.59 0.01
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 9.17 (kBtu/h) 11.92 (kBtu/h) 222.48 288.17 1/21 09:30:00 -11.74 0.0
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN Cooling 0.35 (ton) 0.38 (ton) 190.7 209.77 7/21 20:00:00 76.91 0.01
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN Heating 6.71 (kBtu/h) 8.73 (kBtu/h) 158.92 207.65 1/21 09:00:00 -11.74 0.0
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.31 (ton) 0.34 (ton) 173.75 190.7 7/21 20:00:00 76.91 0.01
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 6.75 (kBtu/h) 8.78 (kBtu/h) 163.15 211.89 1/21 09:30:00 -11.74 0.0
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.31 (ton) 0.34 (ton) 169.51 186.46 7/21 20:00:00 76.91 0.01
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 6.75 (kBtu/h) 8.77 (kBtu/h) 163.15 211.89 1/21 09:30:00 -11.74 0.0
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.57 (ton) 0.62 (ton) 313.59 345.38 7/21 09:00:00 75.99 0.01
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 9.77 (kBtu/h) 12.7 (kBtu/h) 235.2 307.24 1/21 09:30:00 -11.74 0.0
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.64 (ton) 0.7 (ton) 353.85 387.76 7/21 17:00:00 83.59 0.01
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 9.83 (kBtu/h) 12.78 (kBtu/h) 237.31 309.36 1/21 09:30:00 -11.74 0.0
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.42 (ton) 0.46 (ton) 230.96 254.27 7/21 13:30:00 85.71 0.01
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 6.75 (kBtu/h) 8.78 (kBtu/h) 163.15 211.89 1/21 09:30:00 -11.74 0.0
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.42 (ton) 0.46 (ton) 233.08 256.38 7/21 13:15:00 85.48 0.01
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 6.75 (kBtu/h) 8.77 (kBtu/h) 163.15 211.89 1/21 09:30:00 -11.74 0.0
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.61 (ton) 0.67 (ton) 336.9 370.8 7/21 13:15:00 85.48 0.01
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 9.77 (kBtu/h) 12.7 (kBtu/h) 235.2 307.24 1/21 09:30:00 -11.74 0.0
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.73 (ton) 0.8 (ton) 404.71 444.96 7/21 17:00:00 83.59 0.01
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 9.83 (kBtu/h) 12.78 (kBtu/h) 237.31 309.36 1/21 09:30:00 -11.74 0.0
SP-G CORRIDOR SYS-6 FLR-5 SCH-G HPLCMT-EAST ZN Cooling 0.38 (ton) 0.42 (ton) 211.89 233.08 7/21 09:00:00 75.99 0.01
SP-G CORRIDOR SYS-6 FLR-5 SCH-G HPLCMT-EAST ZN Heating 6.17 (kBtu/h) 8.02 (kBtu/h) 146.2 190.7 1/21 09:00:00 -11.74 0.0
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.26 (ton) 0.28 (ton) 141.96 154.68 7/21 20:00:00 76.91 0.01
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 5.42 (kBtu/h) 7.04 (kBtu/h) 131.37 169.51 1/21 09:30:00 -11.74 0.0
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.25 (ton) 0.27 (ton) 137.73 152.56 7/21 20:00:00 76.91 0.01
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 5.42 (kBtu/h) 7.04 (kBtu/h) 131.37 169.51 1/21 09:30:00 -11.74 0.0
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.6 (ton) 0.66 (ton) 330.55 362.33 7/21 09:00:00 75.99 0.01
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 8.0 (kBtu/h) 10.4 (kBtu/h) 188.58 245.79 1/21 09:00:00 -11.74 0.0
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.62 (ton) 0.68 (ton) 343.26 377.16 7/21 17:00:00 83.59 0.01
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 8.05 (kBtu/h) 10.46 (kBtu/h) 190.7 247.91 1/21 09:00:00 -11.74 0.0
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Cooling 0.4 (ton) 0.44 (ton) 220.36 243.67 7/21 13:00:00 85.26 0.01
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Heating 5.42 (kBtu/h) 7.04 (kBtu/h) 131.37 169.51 1/21 09:30:00 -11.74 0.0
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Cooling 0.41 (ton) 0.46 (ton) 228.84 252.15 7/21 13:00:00 85.26 0.01
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Heating 5.36 (kBtu/h) 6.97 (kBtu/h) 129.25 167.39 1/21 09:30:00 -11.74 0.0
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Cooling 0.7 (ton) 0.77 (ton) 385.64 425.89 7/21 16:45:00 83.95 0.01
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Heating 8.05 (kBtu/h) 10.47 (kBtu/h) 190.7 247.91 1/21 09:00:00 -11.74 0.0
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN Cooling 0.33 (ton) 0.37 (ton) 184.34 203.41 7/21 20:00:00 76.91 0.01
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN Heating 5.62 (kBtu/h) 7.3 (kBtu/h) 133.49 173.75 1/21 09:00:00 -11.74 0.0
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.3 (ton) 0.33 (ton) 165.27 182.22 7/21 20:00:00 76.91 0.01
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 5.82 (kBtu/h) 7.57 (kBtu/h) 139.85 182.22 1/21 09:30:00 -11.74 0.0
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.3 (ton) 0.33 (ton) 163.15 180.1 7/21 20:00:00 76.91 0.01
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 5.82 (kBtu/h) 7.57 (kBtu/h) 139.85 182.22 1/21 09:30:00 -11.74 0.0
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.57 (ton) 0.63 (ton) 315.71 347.5 7/21 09:00:00 75.99 0.01
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 8.75 (kBtu/h) 11.38 (kBtu/h) 211.89 275.45 1/21 09:30:00 -11.74 0.0
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.62 (ton) 0.68 (ton) 343.26 377.16 7/21 17:00:00 83.59 0.01
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 8.81 (kBtu/h) 11.46 (kBtu/h) 211.89 277.57 1/21 09:30:00 -11.74 0.0
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.41 (ton) 0.45 (ton) 224.6 247.91 7/21 13:15:00 85.48 0.01
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 5.82 (kBtu/h) 7.57 (kBtu/h) 139.85 182.22 1/21 09:30:00 -11.74 0.0
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.41 (ton) 0.45 (ton) 226.72 250.03 7/21 13:15:00 85.48 0.01
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 5.82 (kBtu/h) 7.57 (kBtu/h) 139.85 182.22 1/21 09:30:00 -11.74 0.0
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.6 (ton) 0.66 (ton) 330.55 364.45 7/21 09:00:00 75.99 0.01
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 8.75 (kBtu/h) 11.38 (kBtu/h) 211.89 275.45 1/21 09:30:00 -11.74 0.0
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.71 (ton) 0.78 (ton) 391.99 432.25 7/21 17:00:00 83.59 0.01
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 8.81 (kBtu/h) 11.46 (kBtu/h) 211.89 277.57 1/21 09:30:00 -11.74 0.0
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN Cooling 0.89 (ton) 0.98 (ton) 493.7 542.43 7/21 10:00:00 79.14 0.01
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN Heating 8.59 (kBtu/h) 11.17 (kBtu/h) 203.41 264.86 1/21 08:00:00 -11.74 0.0
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN Cooling 0.52 (ton) 0.58 (ton) 290.29 317.83 7/21 15:15:00 85.91 0.01
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN Heating 11.6 (kBtu/h) 15.08 (kBtu/h) 275.45 358.09 1/21 09:00:00 -11.74 0.0
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.43 (ton) 0.47 (ton) 239.43 262.74 7/21 14:15:00 86.18 0.01
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 10.57 (kBtu/h) 13.74 (kBtu/h) 250.03 326.31 1/21 09:00:00 -11.74 0.0
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.43 (ton) 0.47 (ton) 237.31 262.74 7/21 14:00:00 86.18 0.01
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 10.57 (kBtu/h) 13.74 (kBtu/h) 250.03 326.31 1/21 09:00:00 -11.74 0.0
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.8 (ton) 0.88 (ton) 442.85 487.34 7/21 09:00:00 75.99 0.01
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 13.4 (kBtu/h) 17.41 (kBtu/h) 317.83 413.18 1/21 09:00:00 -11.74 0.0
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.87 (ton) 0.96 (ton) 483.1 529.72 7/21 16:15:00 84.7 0.01
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 13.45 (kBtu/h) 17.49 (kBtu/h) 319.95 415.3 1/21 09:00:00 -11.74 0.0
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.67 (ton) 0.74 (ton) 372.92 408.94 7/21 13:00:00 85.26 0.01
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 10.57 (kBtu/h) 13.74 (kBtu/h) 250.03 326.31 1/21 09:00:00 -11.74 0.0
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.68 (ton) 0.74 (ton) 375.04 411.06 7/21 13:00:00 85.26 0.01
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 10.57 (kBtu/h) 13.74 (kBtu/h) 250.03 326.31 1/21 09:00:00 -11.74 0.0
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.84 (ton) 0.92 (ton) 464.03 510.65 7/21 09:15:00 76.77 0.01
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 13.4 (kBtu/h) 17.41 (kBtu/h) 317.83 413.18 1/21 09:00:00 -11.74 0.0
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.96 (ton) 1.05 (ton) 529.72 582.69 7/21 15:45:00 85.35 0.01
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 13.45 (kBtu/h) 17.49 (kBtu/h) 319.95 415.3 1/21 09:00:00 -11.74 0.0

Zone Equipment Detail


Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Air Loops Detail


Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:AirLoopHVAC:OutdoorAirSystem Autosized cfm Minimum Outdoor Air Flow Rate 0.00 cfm
OS:Coil:Cooling:DX:SingleSpeed Autosized Btu/h Rated COP 3.45 COP
OS:Coil:Heating:Electric Autosized Btu/h Efficiency 1.00
OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O
OS:SetpointManager:Scheduled Control Variable - Temperature 68.0 to 68.0 F
(demand)
Thermal Zones Total Floor Area 82,565 ft^2 88
Thermal Zones thermostat ranges for cooling 75.2 to 75.2 F
Thermal Zones thermostat ranges for heating 64.4 to 71.6 F
Terminal Types Used OS:AirTerminal:SingleDuct:Uncontrolled 88
(controls)
HVAC Operation Schedule Make-up air unit Occ Sch
Night Cycle Setting CycleOnAny Choice
Economizer Setting DifferentialEnthalpy Choice
Demand Controlled Ventilation Status false Bool

Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:AirLoopHVAC:OutdoorAirSystem Autosized cfm Minimum Outdoor Air Flow Rate 0.00 cfm
OS:Coil:Cooling:Water Autosized gal/min Plant Loop Chilled Water Loop
OS:Coil:Heating:Electric Autosized Btu/h Efficiency 1.00
OS:Fan:VariableVolume Autosized cfm Pressure Rise 5.85 inH_{2}O
OS:SetpointManager:Scheduled Control Variable - Temperature 55.4 to 55.4 F
(demand)
Thermal Zones Total Floor Area 1,786 ft^2 2
Thermal Zones thermostat ranges for cooling 75.2 to 95.0 F
Thermal Zones thermostat ranges for heating 64.4 to 71.6 F
Terminal Types Used OS:AirTerminal:SingleDuct:VAV:Reheat 2
(controls)
HVAC Operation Schedule VAV with Reheat Occ Sch
Night Cycle Setting CycleOnAny Choice
Economizer Setting NoEconomizer Choice
Demand Controlled Ventilation Status false Bool

Plant Loops Detail


Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:Pump:ConstantSpeed Autosized gal/min Rated Power Consumption Autosized W
OS:Chiller:Electric:EIR 23,319.66 Btu/h Reference COP 4.50
OS:Chiller:Electric:EIR (cont) Chiller Source Condenser Water Loop
OS:SetpointManager:Scheduled Control Variable - Temperature 44.6 to 44.6 F
OS:Chiller:Electric:EIR 0.00 Btu/h Reference COP 4.50
OS:Chiller:Electric:EIR (cont) Chiller Source Condenser Water Loop
(demand)
OS:Coil:Cooling:Water Air Loop VAV with Reheat
(controls)
Loop Flow Rate Range Autosized gal/min Minimum Loop Flow Rate 0.0 gal/min
Loop Temperature Range 32.0 to 212.0 F
Design Loop Exit Temperature 44.60 F
Loop Design Temperature Difference 10.80 R

Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:Pump:ConstantSpeed Autosized gal/min Rated Power Consumption Autosized W
OS:CoolingTower:SingleSpeed - Air Autosized gal/min
OS:CoolingTower:SingleSpeed (cont) - Water Autosized cfm Fan Power at Design Air Flow Rate 265,452.45 W
OS:SetpointManager:Scheduled Control Variable - Temperature 84.2 to 84.2 F
(demand)
OS:Chiller:Electric:EIR Plant Loop Chilled Water Loop
OS:Chiller:Electric:EIR Plant Loop Chilled Water Loop
(controls)
Loop Flow Rate Range Autosized gal/min Minimum Loop Flow Rate 0.0 gal/min
Loop Temperature Range 32.0 to 212.0 F
Design Loop Exit Temperature 84.20 F
Loop Design Temperature Difference 10.80 R

Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:Pump:ConstantSpeed Autosized gal/min Rated Power Consumption Autosized W
OS:WaterHeater:Mixed 600 gal Heater Thermal Efficiency 1.00 fraction
OS:SetpointManager:Scheduled Control Variable - Temperature 140.0 to 140.0 F
(demand)
OS:WaterUse:Connections Water Use Connections 1
OS:WaterUse:Connections Water Use Connections 2
OS:WaterUse:Connections Water Use Connections 3
OS:WaterUse:Connections Water Use Connections 4
OS:WaterUse:Connections Water Use Connections 5
OS:WaterUse:Connections Water Use Connections 6
OS:WaterUse:Connections Water Use Connections 7
OS:WaterUse:Connections Water Use Connections 8
OS:WaterUse:Connections Water Use Connections 9
OS:WaterUse:Connections Water Use Connections 10
OS:WaterUse:Connections Water Use Connections 11
OS:WaterUse:Connections Water Use Connections 12
OS:WaterUse:Connections Water Use Connections 13
OS:WaterUse:Connections Water Use Connections 14
OS:WaterUse:Connections Water Use Connections 15
OS:WaterUse:Connections Water Use Connections 16
OS:WaterUse:Connections Water Use Connections 17
OS:WaterUse:Connections Water Use Connections 18
OS:WaterUse:Connections Water Use Connections 19
OS:WaterUse:Connections Water Use Connections 20
OS:WaterUse:Connections Water Use Connections 21
OS:WaterUse:Connections Water Use Connections 22
OS:WaterUse:Connections Water Use Connections 23
OS:WaterUse:Connections Water Use Connections 24
OS:WaterUse:Connections Water Use Connections 25
OS:WaterUse:Connections Water Use Connections 26
OS:WaterUse:Connections Water Use Connections 27
OS:WaterUse:Connections Water Use Connections 28
OS:WaterUse:Connections Water Use Connections 29
OS:WaterUse:Connections Water Use Connections 30
OS:WaterUse:Connections Water Use Connections 31
OS:WaterUse:Connections Water Use Connections 32
OS:WaterUse:Connections Water Use Connections 33
OS:WaterUse:Connections Water Use Connections 34
OS:WaterUse:Connections Water Use Connections 35
OS:WaterUse:Connections Water Use Connections 36
OS:WaterUse:Connections Water Use Connections 37
OS:WaterUse:Connections Water Use Connections 38
OS:WaterUse:Connections Water Use Connections 39
OS:WaterUse:Connections Water Use Connections 40
OS:WaterUse:Connections Water Use Connections 41
OS:WaterUse:Connections Water Use Connections 42
OS:WaterUse:Connections Water Use Connections 43
OS:WaterUse:Connections Water Use Connections 44
OS:WaterUse:Connections Water Use Connections 45
OS:WaterUse:Connections Water Use Connections 46
OS:WaterUse:Connections Water Use Connections 47
OS:WaterUse:Connections Water Use Connections 48
OS:WaterUse:Connections Water Use Connections 49
OS:WaterUse:Connections Water Use Connections 50
OS:WaterUse:Connections Water Use Connections 51
OS:WaterUse:Connections Water Use Connections 52
OS:WaterUse:Connections Water Use Connections 53
OS:WaterUse:Connections Water Use Connections 54
OS:WaterUse:Connections Water Use Connections 55
OS:WaterUse:Connections Water Use Connections 56
OS:WaterUse:Connections Water Use Connections 57
OS:WaterUse:Connections Water Use Connections 58
OS:WaterUse:Connections Water Use Connections 59
OS:WaterUse:Connections Water Use Connections 60
OS:WaterUse:Connections Water Use Connections 61
OS:WaterUse:Connections Water Use Connections 62
OS:WaterUse:Connections Water Use Connections 63
OS:WaterUse:Connections Water Use Connections 64
OS:WaterUse:Connections Water Use Connections 65
OS:WaterUse:Connections Water Use Connections 66
OS:WaterUse:Connections Water Use Connections 67
OS:WaterUse:Connections Water Use Connections 68
OS:WaterUse:Connections Water Use Connections 69
OS:WaterUse:Connections Water Use Connections 70
OS:WaterUse:Connections Water Use Connections 71
OS:WaterUse:Connections Water Use Connections 72
OS:WaterUse:Connections Water Use Connections 73
OS:WaterUse:Connections Water Use Connections 74
OS:WaterUse:Connections Water Use Connections 75
OS:WaterUse:Connections Water Use Connections 76
OS:WaterUse:Connections Water Use Connections 77
OS:WaterUse:Connections Water Use Connections 78
OS:WaterUse:Connections Water Use Connections 79
OS:WaterUse:Connections Water Use Connections 80
(controls)
Loop Flow Rate Range Autosized gal/min Minimum Loop Flow Rate 0.0 gal/min
Loop Temperature Range 50.0 to 140.0 F
Design Loop Exit Temperature 140.00 F
Loop Design Temperature Difference 9.00 R

Outdoor Air


Average Number of Occupants Nominal Number of Occupants Zone Volume (ft^3) Avg. Mechanical Ventilation (ach) Min. Mechanical Ventilation (ach) Avg. Infiltration (ach) Min. Infiltration (ach) Avg. Simple Ventilation (ach) Min. Simple Ventilation (ach)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.433 0.353 0.015 0.0 0.0 0.0
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.472 0.398 0.045 0.0 0.0 0.0
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.473 0.398 0.045 0.0 0.0 0.0
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.469 0.397 0.075 0.0 0.0 0.0
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.465 0.397 0.075 0.0 0.0 0.0
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.498 0.401 0.046 0.0 0.0 0.0
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.498 0.401 0.046 0.0 0.0 0.0
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.495 0.398 0.075 0.0 0.0 0.0
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.484 0.398 0.075 0.0 0.0 0.0
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.435 0.353 0.018 0.0 0.0 0.0
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.474 0.398 0.054 0.0 0.0 0.0
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.475 0.398 0.054 0.0 0.0 0.0
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.47 0.397 0.089 0.0 0.0 0.0
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.465 0.397 0.089 0.0 0.0 0.0
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.5 0.401 0.054 0.0 0.0 0.0
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.5 0.401 0.054 0.0 0.0 0.0
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.497 0.398 0.089 0.0 0.0 0.0
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.485 0.398 0.089 0.0 0.0 0.0
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.436 0.353 0.02 0.0 0.0 0.0
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.474 0.398 0.06 0.0 0.0 0.0
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.475 0.398 0.06 0.0 0.0 0.0
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.47 0.397 0.1 0.0 0.0 0.0
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.465 0.397 0.1 0.0 0.0 0.0
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.5 0.401 0.06 0.0 0.0 0.0
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.499 0.401 0.06 0.0 0.0 0.0
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.496 0.398 0.1 0.0 0.0 0.0
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.485 0.398 0.1 0.0 0.0 0.0
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.435 0.353 0.023 0.0 0.0 0.0
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.473 0.398 0.07 0.0 0.0 0.0
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.473 0.398 0.07 0.0 0.0 0.0
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.469 0.397 0.116 0.0 0.0 0.0
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.464 0.397 0.116 0.0 0.0 0.0
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.498 0.4 0.07 0.0 0.0 0.0
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.497 0.4 0.07 0.0 0.0 0.0
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.495 0.397 0.116 0.0 0.0 0.0
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.483 0.398 0.116 0.0 0.0 0.0
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.434 0.353 0.024 0.0 0.0 0.0
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.472 0.397 0.074 0.0 0.0 0.0
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.471 0.397 0.074 0.0 0.0 0.0
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.469 0.397 0.122 0.0 0.0 0.0
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.464 0.397 0.122 0.0 0.0 0.0
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.497 0.4 0.074 0.0 0.0 0.0
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.496 0.4 0.074 0.0 0.0 0.0
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.494 0.397 0.122 0.0 0.0 0.0
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.482 0.397 0.122 0.0 0.0 0.0
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.432 0.353 0.025 0.0 0.0 0.0
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.469 0.397 0.077 0.0 0.0 0.0
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.469 0.397 0.077 0.0 0.0 0.0
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.468 0.397 0.128 0.0 0.0 0.0
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.463 0.397 0.128 0.0 0.0 0.0
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.494 0.4 0.078 0.0 0.0 0.0
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.494 0.4 0.078 0.0 0.0 0.0
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.493 0.397 0.128 0.0 0.0 0.0
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.481 0.397 0.128 0.0 0.0 0.0
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.426 0.353 0.027 0.0 0.0 0.0
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.463 0.397 0.081 0.0 0.0 0.0
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.463 0.397 0.081 0.0 0.0 0.0
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.467 0.397 0.134 0.0 0.0 0.0
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.46 0.397 0.134 0.0 0.0 0.0
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.487 0.399 0.081 0.0 0.0 0.0
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.487 0.399 0.081 0.0 0.0 0.0
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.485 0.397 0.134 0.0 0.0 0.0
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.476 0.397 0.134 0.0 0.0 0.0
SP-G CORRIDOR SYS-6 FLR-5 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.128 0.0 0.01 0.0 0.0 0.0
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.46 0.398 0.032 0.0 0.0 0.0
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.46 0.398 0.032 0.0 0.0 0.0
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.458 0.397 0.052 0.0 0.0 0.0
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.457 0.397 0.052 0.0 0.0 0.0
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.486 0.4 0.032 0.0 0.0 0.0
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.485 0.4 0.032 0.0 0.0 0.0
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.478 0.398 0.053 0.0 0.0 0.0
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.436 0.353 0.022 0.0 0.0 0.0
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.474 0.398 0.065 0.0 0.0 0.0
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.474 0.398 0.065 0.0 0.0 0.0
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.47 0.397 0.108 0.0 0.0 0.0
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.465 0.397 0.108 0.0 0.0 0.0
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.499 0.401 0.066 0.0 0.0 0.0
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.498 0.4 0.066 0.0 0.0 0.0
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.496 0.398 0.108 0.0 0.0 0.0
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.484 0.398 0.108 0.0 0.0 0.0
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 2.37 4.42 9498 0.604 0.336 0.056 0.0 0.0 0.0
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.4 0.35 0.237 0.0 0.0 0.0
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.445 0.396 0.292 0.0 0.0 0.0
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.445 0.396 0.292 0.0 0.0 0.0
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.454 0.396 0.347 0.0 0.0 0.0
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.452 0.396 0.347 0.0 0.0 0.0
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.462 0.396 0.293 0.0 0.0 0.0
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.462 0.396 0.293 0.0 0.0 0.0
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.469 0.396 0.348 0.0 0.0 0.0
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.465 0.396 0.348 0.0 0.0 0.0

Cash Flow

No Data to Show for Cash Flow

Site and Source Summary


Total Energy (kBtu) Energy Per Total Building Area (kBtu/ft^2) Energy Per Conditioned Building Area (kBtu/ft^2)
Total Site Energy 3592975.7 42.6 42.6
Net Site Energy 3592975.7 42.6 42.6
Total Source Energy 11378942.5 134.9 134.9
Net Source Energy 11378942.5 134.9 134.9

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613

Schedule Overview


Schedule Type Limits Rules Use Count
Air Velocity Schedule Velocity 0 3
Always On Dimensionless 0 90
CHW Temp Temperature 3 1
Clothing Schedule ClothingInsulation 1 3
CW Temp Temperature 3 1
Make-up air unit Occ Sch Dimensionless 7 2
Makeup-Air Unit Supply Air Temp Temperature 0 1
NECB-A-Electric-Equipment Dimensionless 3 1
NECB-A-Lighting Dimensionless 3 1
NECB-A-Occupancy Dimensionless 3 1
NECB-A-Service Water Heating Dimensionless 3 1
NECB-A-Thermostat Setpoint-Cooling Temperature 3 3
NECB-A-Thermostat Setpoint-Heating Temperature 3 3
NECB-Activity ActivityLevel 0 90
NECB-G-Electric-Equipment Dimensionless 3 89
NECB-G-Lighting Dimensionless 3 89
NECB-G-Occupancy Dimensionless 3 89
NECB-G-Service Water Heating Dimensionless 3 79
NECB-G-Thermostat Setpoint-Cooling Temperature 3 180
NECB-G-Thermostat Setpoint-Heating Temperature 3 180
ON_OFF_ALWAYS_OFF Availability 3 88
Schedule Ruleset 10 0 1
Schedule Ruleset 100 0 1
Schedule Ruleset 101 0 1
Schedule Ruleset 102 0 1
Schedule Ruleset 103 0 1
Schedule Ruleset 104 0 1
Schedule Ruleset 105 0 1
Schedule Ruleset 106 0 1
Schedule Ruleset 107 0 1
Schedule Ruleset 108 0 1
Schedule Ruleset 109 0 1
Schedule Ruleset 11 0 1
Schedule Ruleset 110 0 1
Schedule Ruleset 111 0 1
Schedule Ruleset 112 0 1
Schedule Ruleset 113 0 1
Schedule Ruleset 114 0 1
Schedule Ruleset 115 0 1
Schedule Ruleset 116 0 1
Schedule Ruleset 117 0 1
Schedule Ruleset 118 0 1
Schedule Ruleset 119 0 1
Schedule Ruleset 12 0 1
Schedule Ruleset 120 0 1
Schedule Ruleset 121 0 1
Schedule Ruleset 122 0 1
Schedule Ruleset 123 0 1
Schedule Ruleset 124 0 1
Schedule Ruleset 125 0 1
Schedule Ruleset 126 0 1
Schedule Ruleset 127 0 1
Schedule Ruleset 128 0 1
Schedule Ruleset 129 0 1
Schedule Ruleset 13 0 1
Schedule Ruleset 130 0 1
Schedule Ruleset 131 0 1
Schedule Ruleset 132 0 1
Schedule Ruleset 133 0 1
Schedule Ruleset 134 0 1
Schedule Ruleset 135 0 1
Schedule Ruleset 136 0 1
Schedule Ruleset 137 0 1
Schedule Ruleset 138 0 1
Schedule Ruleset 139 0 1
Schedule Ruleset 14 0 1
Schedule Ruleset 140 0 1
Schedule Ruleset 141 0 1
Schedule Ruleset 142 0 1
Schedule Ruleset 143 0 1
Schedule Ruleset 144 0 1
Schedule Ruleset 145 0 1
Schedule Ruleset 146 0 1
Schedule Ruleset 147 0 1
Schedule Ruleset 148 0 1
Schedule Ruleset 149 0 1
Schedule Ruleset 15 0 1
Schedule Ruleset 150 0 1
Schedule Ruleset 151 0 1
Schedule Ruleset 152 0 1
Schedule Ruleset 153 0 1
Schedule Ruleset 154 0 1
Schedule Ruleset 155 0 1
Schedule Ruleset 156 0 1
Schedule Ruleset 157 0 1
Schedule Ruleset 158 0 1
Schedule Ruleset 159 0 1
Schedule Ruleset 16 0 1
Schedule Ruleset 160 0 1
Schedule Ruleset 161 0 1
Schedule Ruleset 162 0 1
Schedule Ruleset 163 0 1
Schedule Ruleset 164 0 1
Schedule Ruleset 165 0 1
Schedule Ruleset 166 0 1
Schedule Ruleset 167 0 1
Schedule Ruleset 168 0 1
Schedule Ruleset 169 0 1
Schedule Ruleset 17 0 1
Schedule Ruleset 170 0 1
Schedule Ruleset 171 0 1
Schedule Ruleset 172 0 1
Schedule Ruleset 173 0 1
Schedule Ruleset 174 0 1
Schedule Ruleset 175 0 1
Schedule Ruleset 176 0 1
Schedule Ruleset 177 0 1
Schedule Ruleset 178 0 1
Schedule Ruleset 179 0 1
Schedule Ruleset 18 0 1
Schedule Ruleset 180 0 1
Schedule Ruleset 181 0 1
Schedule Ruleset 182 0 1
Schedule Ruleset 183 0 1
Schedule Ruleset 184 0 1
Schedule Ruleset 185 0 1
Schedule Ruleset 186 0 1
Schedule Ruleset 187 0 1
Schedule Ruleset 188 0 1
Schedule Ruleset 189 0 1
Schedule Ruleset 19 0 1
Schedule Ruleset 190 0 1
Schedule Ruleset 191 0 1
Schedule Ruleset 192 0 1
Schedule Ruleset 193 0 1
Schedule Ruleset 194 0 1
Schedule Ruleset 195 0 1
Schedule Ruleset 196 0 1
Schedule Ruleset 197 0 1
Schedule Ruleset 198 0 1
Schedule Ruleset 199 0 1
Schedule Ruleset 20 0 1
Schedule Ruleset 200 0 1
Schedule Ruleset 201 0 1
Schedule Ruleset 202 0 1
Schedule Ruleset 203 0 1
Schedule Ruleset 204 0 1
Schedule Ruleset 205 0 1
Schedule Ruleset 206 0 1
Schedule Ruleset 207 0 1
Schedule Ruleset 208 0 1
Schedule Ruleset 209 0 1
Schedule Ruleset 21 0 1
Schedule Ruleset 210 0 1
Schedule Ruleset 211 0 1
Schedule Ruleset 212 0 1
Schedule Ruleset 213 0 1
Schedule Ruleset 214 0 1
Schedule Ruleset 215 0 1
Schedule Ruleset 216 0 1
Schedule Ruleset 217 0 1
Schedule Ruleset 218 0 1
Schedule Ruleset 219 0 1
Schedule Ruleset 22 0 1
Schedule Ruleset 220 0 1
Schedule Ruleset 221 0 1
Schedule Ruleset 222 0 1
Schedule Ruleset 223 0 1
Schedule Ruleset 224 0 1
Schedule Ruleset 225 0 1
Schedule Ruleset 226 0 1
Schedule Ruleset 227 0 1
Schedule Ruleset 228 0 1
Schedule Ruleset 229 0 1
Schedule Ruleset 23 0 1
Schedule Ruleset 230 0 1
Schedule Ruleset 231 0 1
Schedule Ruleset 232 0 1
Schedule Ruleset 233 0 1
Schedule Ruleset 234 0 1
Schedule Ruleset 235 0 1
Schedule Ruleset 236 0 1
Schedule Ruleset 237 0 1
Schedule Ruleset 238 0 1
Schedule Ruleset 239 0 1
Schedule Ruleset 24 0 1
Schedule Ruleset 240 0 1
Schedule Ruleset 241 0 1
Schedule Ruleset 242 0 1
Schedule Ruleset 25 0 1
Schedule Ruleset 26 0 1
Schedule Ruleset 27 0 1
Schedule Ruleset 28 0 1
Schedule Ruleset 29 0 1
Schedule Ruleset 3 0 1
Schedule Ruleset 30 0 1
Schedule Ruleset 31 0 1
Schedule Ruleset 32 0 1
Schedule Ruleset 33 0 1
Schedule Ruleset 34 0 1
Schedule Ruleset 35 0 1
Schedule Ruleset 36 0 1
Schedule Ruleset 37 0 1
Schedule Ruleset 38 0 1
Schedule Ruleset 39 0 1
Schedule Ruleset 4 0 1
Schedule Ruleset 40 0 1
Schedule Ruleset 41 0 1
Schedule Ruleset 42 0 1
Schedule Ruleset 43 0 1
Schedule Ruleset 44 0 1
Schedule Ruleset 45 0 1
Schedule Ruleset 46 0 1
Schedule Ruleset 47 0 1
Schedule Ruleset 48 0 1
Schedule Ruleset 49 0 1
Schedule Ruleset 5 0 1
Schedule Ruleset 50 0 1
Schedule Ruleset 51 0 1
Schedule Ruleset 52 0 1
Schedule Ruleset 53 0 1
Schedule Ruleset 54 0 1
Schedule Ruleset 55 0 1
Schedule Ruleset 56 0 1
Schedule Ruleset 57 0 1
Schedule Ruleset 58 0 1
Schedule Ruleset 59 0 1
Schedule Ruleset 6 0 1
Schedule Ruleset 60 0 1
Schedule Ruleset 61 0 1
Schedule Ruleset 62 0 1
Schedule Ruleset 63 0 1
Schedule Ruleset 64 0 1
Schedule Ruleset 65 0 1
Schedule Ruleset 66 0 1
Schedule Ruleset 67 0 1
Schedule Ruleset 68 0 1
Schedule Ruleset 69 0 1
Schedule Ruleset 7 0 1
Schedule Ruleset 70 0 1
Schedule Ruleset 71 0 1
Schedule Ruleset 72 0 1
Schedule Ruleset 73 0 1
Schedule Ruleset 74 0 1
Schedule Ruleset 75 0 1
Schedule Ruleset 76 0 1
Schedule Ruleset 77 0 1
Schedule Ruleset 78 0 1
Schedule Ruleset 79 0 1
Schedule Ruleset 8 0 1
Schedule Ruleset 80 0 1
Schedule Ruleset 81 0 1
Schedule Ruleset 82 0 1
Schedule Ruleset 83 0 1
Schedule Ruleset 84 0 1
Schedule Ruleset 85 0 1
Schedule Ruleset 86 0 1
Schedule Ruleset 87 0 1
Schedule Ruleset 88 0 1
Schedule Ruleset 89 0 1
Schedule Ruleset 9 0 1
Schedule Ruleset 90 0 1
Schedule Ruleset 91 0 1
Schedule Ruleset 92 0 1
Schedule Ruleset 93 0 1
Schedule Ruleset 94 0 1
Schedule Ruleset 95 0 1
Schedule Ruleset 96 0 1
Schedule Ruleset 97 0 1
Schedule Ruleset 98 0 1
Schedule Ruleset 99 0 1
Service Water Loop Temp - 140F Temperature 0 2
Supply Air Temp Temperature 0 1
VAV with Reheat Occ Sch Dimensionless 7 2
Water Heater Ambient Temp Schedule - 70F Temperature 0 1
Work Efficiency Schedule Dimensionless 0 3